Product details

| IEC designation | U40B/110 | |
| Diameter D | mm | 178 |
| Height H | mm | 110 |
| Creepage distance L | mm | 185 |
| Socket coupling | mm | 11 |
| Mechanical failing load | kn | 40 |
| Mechanical routine test | kn | 20 |
| Wet power frequency withstand voltage | kv | 25 |
| Dry lightning impulse withstand voltage | kv | 50 |
| Impulse puncture voltage | P.U | 2.8 |
| Power frequency puncture voltage | kv | 90 |
| Radio influence voltage | μv | 50 |
| Corona visual test | kv | 18/22 |
| Power frequency electric arc voltage | ka | 0.12s/20kA |
| Net weight per unit | kg | 2.1 |
Product Message